LINAC WATER SYSTEMS MAINTENANCE RECORDS
Date Requestor System(s) Item Work Performed Comments Details
Sept, 2003 Dortwegt L1:WS1 Pump Replaced mech seal    
May, 2004 Dortwegt L2/L4/L5:WS1 Pump Replaced mech seal    
7/12/2004 Dortwegt L5:WS1 Pump Replaced mech seal    
Sept, 2004 Dortwegt L1:WS1 Filter housing Initial installation Element PM010-20AA-DO, Parker, 1 micron, qty 6, full pump flow Clean DP = 1 psid
Sept, 2004 Dortwegt L2/L4/L5:WS1 Filter housing Initial installation Element PM010-30AA-DO, Parker, 1 micron, qty 6, full pump flow Clean DP = 2 psid (all units)
Sept, 2004 Dortwegt L1:WS1 Resins Refreshed resins Mixed bed and dissolved oxygen; also added 3.5 cu. Ft. mixed bed System at 16.0 Mohm on 10-7-04
Sept, 2004 Dortwegt L2:WS1 Resins Refreshed resins Mixed bed and dissolved oxygen; also added 3.5 cu. Ft. mixed bed System at 14.8 Mohm on 10-7-04
Sept, 2004 Dortwegt L4:WS1 Resins Refreshed resins Mixed bed and dissolved oxygen; also added 3.5 cu. Ft. mixed bed System at 15.7 Mohm on 10-7-04
Sept, 2004 Dortwegt L5:WS1 Resins Refreshed resins Mixed bed and dissolved oxygen; also added 3.5 cu. Ft. mixed bed System at 16.0 Mohm on 10-7-04
Sept, 2004 Dortwegt L1:WS1 Filter housing (resins) Initial installation Element PM010-10AA-DO, Parker, 1 micron, qty 1 Clean DP = 3 psid
Sept, 2004 Dortwegt L2/L4/L5:WS1 Filter housing (resins) Initial installation Element PM010-10AA-DO, Parker, 1 micron, qty 1 Clean DP = 2 psid (all units)
Sept, 2004 Dortwegt L1/L2:WS1 Resistivity meters Initial installation Thornton 200CR (channel A = L1, channel B = L2)  
Sept, 2004 Dortwegt L4/L5:WS1 Resistivity meters Initial installation Thornton 200CR (channel A = L4, channel B = L5)  
Sept, 2004 Dortwegt L1/L2/L5:WS1 HX Griswolds Cleaned    
9/15/2004 Dortwegt L2:WS1 Relief valve Replace RV on ckt for L2:RL/DL  
9/15/2004 Dortwegt L2:WS1 Pressure gage Replace 0-25 psig gage in tunnel leaking glycerine  
9/16/2004 Dortwegt L1:WS1 Circulator flow Removed coil Removed 3/16" flow regulating coil due to unstable flow Flow increased from 0.7 to 1.7 gpm
10/8/2004 Cours/Douell Klystron hot spare Water ckts Hydrotesting Working with Alex Cours and Mike Douell LinacHydroRpt100804.doc